Riello Dialog Plus DLP series Especificaciones Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 34
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
SPEDLPX0205REN
18
DIALOG PLUS
> 8.3 Configuration software
Configuration Software
UPSTools software enables the user to configure the UPS, and provides a full view of the system
parameters and status through the RS232 serial port.
Refer to the paragraph UPS Configuration for a list of the configurable values available.
UPS Configuration
The following table lists all of the possible configurable values available so as to best adapt the UPS to the
user requirements. The configuration can only be modified using the UPSTools software provided.
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
Automatic Restart
Automatic restart when
the mains power supply
returns
Enabled.
Disabled
Enabled
Battery low alarm
Remaining battery charge
level setting for the
battery low alarm
3 min.
1 – 99 in steps of 1 minute
Output frequency
Enables the user to select
the output frequency.
50Hz
50Hz
60Hz
Auto(the UPS will set the output to
match the input frequency either 50 or
60 Hz)
Output voltage
Enables the user to select
the output voltage
230 Vac
220 Vac
230 Vac
240 Vac
Bypass voltage
threshold
Selects the voltage range
accepted for switching
over to the bypass
Low: 180V
High: 264V
Low: 180 – 200 in steps of 1V
High: 250 – 264 in steps of 1V
Battery capacity
Enables the user to set
the capacity of battery
Standard:
7.2Ah
ER: 65Ah
The user must set the capacity of the battery
if the actual capacity is different from the
default value.
Vista de pagina 17