11
PD 30PDP 45PDP 65
POWER 300VA/195W450VA/260W650VA/410W
INPUT
Rated voltage 220 – 240 Vac
Voltage range 230 Vac (-18%, +15%) 230 Vac (-22%, +15%)
Frequency 50/60 Hz with autorange
OUTPUT
Voltage in mains operation Equal to mains supply value 230 Vac (-13%, +11%)
Voltage in battery operation 230 Vac ±5%
Frequency in battery operation 50 or 60 Hz ±0.1%
Transfer time typical 2 ms, maximum 4 ms
Waveform from battery Pseudo sinewave
BATTERIES
Type Maintenance-free sealed lead-acid
Recharge time 4-6 h
OTHER DATA
Protection Battery low – overcurrent – short-circuit
Safety compliance EN 50091-1-1 and Council Directive 73 / 23 EEC
EMC conformance EN 50091 - 2 cl. B and Council Directive 89 / 336 EEC
Surge capability IEC 801-5
Noise < 40 dBA at 1 mt.
Color Base gray, shell blue
Operating temperature 0 °C / +40 °C
Storage temperature -15 °C / +45 °C
Relative humidity < 90 % non condensing
Description Power Back-up Dimensions Weights Code
(min) (HLP) mm (Kg)
Personal Dialog PD30300VA/195W7-18*137x201x3746UPIN03053XRUB0R
Personal Dialog Pro PDP45450VA/260W10-24*137x201x3746,5UPIN04053XRUB1R
Personal Dialog Pro PDP65650VA/410W8-34*137x201x3749,5UPIN06053XRUB1R
communication software See software section page 66
* According to load applied (see back-up graph)