INSTALLATION, OPERATING
and
SERVICE MANUAL
THE INSTALLATION OF THE UNIT SHALL BE IN ACCORDANCE WITH THE
REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION.
OIL-FIRED BOILER
MODEL: NBR-2001 NBR-2002
HEAD OFFICE
MARKETING / PRODUCTION
Newmac Mfg. Inc.
DEBERT AIR INDUSTRIAL PARK,
LANCASTER CRESCENT
P.O. BOX 9, DEBERT
NOVA SCOTIA, BOM 1G0
PHONE: 902-662-3840
FAX: 902-662-2581
WAREHOUSE
Newmac Mfg. Inc.
430 SPRINGBANK AVE., SOUTH
P.O. BOX 545
WOODSTOCK, ONTARIO
N4S 7Y5
PHONE: 519-539-6147
FAX: 519-539-0048
EMAIL: newmac@newmacfurnaces.com
NOTICE TO HOMEOWNER:
READ THESE INSTRUCTIONS
SAVE THESE INSTRUCTIONS
2210150 REVISED APRIL 2007
Printed: ________________________
Subject to change without notice
Vista de pagina 0
1 2 3 4 5 6 ... 33 34

Indice de contenidos

Pagina 1 - SERVICE MANUAL

INSTALLATION, OPERATINGandSERVICE MANUALTHE INSTALLATION OF THE UNIT SHALL BE IN ACCORDANCE WITH THEREGULATIONS OF THE AUTHORITIES HAVING JURISDICTION

Pagina 2 - GENERAL INSTRUCTIONS

9free area is unknown, assume wood louvers have 20-25% free area and metal louvers and grilles have60-75% free area. Screens should not be less than 1

Pagina 3

10OIL BURNER OPERATING INSTRUCTIONSBURNER CAREThis burner is fully automatic in operation. All adjustments should be made by a qualified technician.Ke

Pagina 4 - BOILER INSTALLATION

11Riello Burner End Cone Protector FIGURE 4 Riello Burner End cone ProtectorRiello burners are equipped with a ceramic fibresleeve to protect the end

Pagina 5

12FIGURE 6 BURNER INSERTION TABLE 2 DIMENSIONAL RELATIONSHIPSMAINTENANCE & SERVICEMaintenance and servicing must be done by a qualified burner tec

Pagina 6

13FIGURE 7 TYPICAL OIL PUMPGAUGEPORTINLETPORTBLEEDPORTINLETPORTRETURN&BY-PASSPORTNOZZLEPORTFLEXIBLE OIL LINEThe flexible oil supply line shipped w

Pagina 7

14FIGURE 8 (a) TYPICAL OIL TANK PIPING INSTALLATIONSFIGURE 8 (b) FLEXIBLE OIL LINE INSTALLATION

Pagina 8

15FIGURE 9 DIMENSIONS & CONTROL LOCATION

Pagina 9

16FIGURE 10 TYPICAL PIPING LAYOUT

Pagina 10

17FIGURE 11 TYPICAL RADIANT FLOOR PIPING LAYOUT

Pagina 11

18FIGURE 12 (a) STANDARD WIRING SCHEMATIC – Riello & Carlin

Pagina 12

1NBR 2001 / NBR 2002GENERAL INSTRUCTIONSIt is the responsibility of the consignee of the unit to examine the package for damage and, if found to note

Pagina 13

19FIGURE 12 (b) STANDARD WIRING SCHEMATIC – Beckett & Aero

Pagina 14

20FIGURE 13 NBR 2001 EXPLODED ASSEMBLY

Pagina 15

21TABLE 3 NBR-2001 / NBR-2002 PARTS LISTItem NBR-2001 PartNo.NBR-2002 PartNo.Description1 A 4110194A 3/16" Pressure Vessel Assembly1 B 4110194 41

Pagina 16

22FIGURE 14 RIELLO F3 & F5 EXPLODED ASSEMBLYFIGURE 15 RIELLO BF3 & BF5 EXPLODED ASSEMBLYItem 49 Riello Burner End Cone Protector not shown. Se

Pagina 17

23TABLE 4 RIELLO BURNER PARTS LISTITEM PART NUMBER BURNER MODEL DESCRIPTIONF3 & F5 BF3 & BF5 RIELLO NEWMAC F3 F5 BF3 BF51 3007232 X Burner bac

Pagina 18

24FIGURE 16 BECKETT BURNER EXPLODED ASSEMBLYTABLE 5 BECKETT BURNER PARTS LISTPART NUMBER BURNER MODELITEM BECKETT NEWMAC AFG70MBSS AFG70MDSS DESCRIPTI

Pagina 19

25FIGURE 17 CARLIN BURNER EXPLODED ASSEMBLYTABLE 6 CARLIN BURNER PARTS LISTPART NUMBER BURNER MODELITEMCARLIN NEWMAC EZ-1 EZ-1 PPDESCRIPTION9785700BNB

Pagina 20

26FIGURE 18 AERO BURNER EXPLODED ASSEMBLYTABLE 7 AERO BURNER PARTS LISTPART NUMBERITEMAERO NEWMACQTYREQ'DDESCRIPTION1 35222100 2090016 1 HF-US Ho

Pagina 21

27FIGURE 19 COMMON CHIMNEY DRAFT PROBLEMS

Pagina 22

28TROUBLESHOOTING CHARTPROBLEM CAUSE CORRECTIONBurner Motor Fails to Start Check for Broken WiresTighten ConnectionsClean ContactsThermostatReplace Th

Pagina 23

2NBR 2001 / NBR 2002GENERAL INSTRUCTIONS*Install Beckett Low Firing Rate Baffle (3708) on AFG70MDSS. † Danfoss AS Nozzle with AFG70MBSS Burner only.Mo

Pagina 24

29TROUBLESHOOTING CHARTPROBLEM CAUSE CORRECTIONNot Enough HeatFiring Rate Too LowUse Higher Input NozzleClean Heat ExchangerDirty Heat ExchangerFlush

Pagina 25

30TROUBLESHOOTING CHARTPROBLEM CAUSE CORRECTIONBurner Pump WhineSuctionLine Air LeakTighten ConnectionsHydronic System NoiseProvide Free MovementInsta

Pagina 26

31IMPORTANT HOMEOWNER INSTRUCTIONS1. AN EMERGENCY POWER SWITCH IS REQUIRED TO BE INSTALLED IN ACONVENIENT LOCATION AT A SAFE DISTANCE FROM THE BURNER.

Pagina 27

32INSTALLER INFORMATIONNAME:COMPANY:INSTALLATION DATE:THE HOMEOWNER SHOULD TELEPHONE ( ) FOR SERVICE ORADDITIONAL INFORMATION.MODEL:1 FUEL INPUT (USGP

Pagina 28

33NBR (LIMITED) B0ILER WARRANTYEffective July 1, 1995 and subject to the following conditions Newmac Manufacturing Inc. warrants the Oil Fired BOILER,

Pagina 29 - TROUBLESHOOTING CHART

3BOILER INSTALLATIONINSTALLATION REGULATIONSThis unit should be installed in accordance with the regulations of the authority having jurisdiction. InC

Pagina 30

4Newmac Sealed Vent SystemConsult the GENERAL INSTRUCTIONS of this manual for approved burners. Follow the instructionssupplied with the SVS system fo

Pagina 31

5GAUGESThe pressure and temperature gauge supplied with the boiler has a 1/4” NPT connection. Refer to Figure9 for its location.TANKLESS DOMESTIC HOT

Pagina 32

6Low Limit Setting: This setting controls the minimum standby temperature. It regulates circulator andburner operation. When the low limit setting is

Pagina 33 - INSTALLER INFORMATION

7MIXING METHODSA method of mixing is required for boiler protection with low temperature systems. The minimum returnwater temperature required is 135

Pagina 34 - NBR (LIMITED) B0ILER WARRANTY

8BLOCKED VENT SWITCHThe WMO-1 blocked vent control is required on Newmac oil-fired and combination furnaces or boilersinstalled in Canada. The WMO-1 s