13
DIALOG ACTIVE
DA 50
DA 75
DA 100
DA 150
DA 200
MODELS DA 50 DA 75 DA 100 DA 150 DA 200
POWER 500VA/335W 750VA/500W 1000VA/670W 1500VA/1000W 2000VA/1340W
INPUT
Rated voltage 230 Vac
Voltage range 230 Vac (-25%, +21%)
Frequency 50/60 Hz auto sensing
Frequency range +/- 5Hz
OUTPUT
Rated voltage 230 Vac
Voltage on mains operation 230 Vac (-15%, +11%)
Frequency 50 - 60 Hz auto sensing
Voltage on battery operation 230 Vac (+/-5%)
Waveform Sinewave
Distortion <2%
BATTERIES
Type VRLA AGM Maintenance-free lead-acid
Recharge time 2-4 h
ENVIRONMENTAL
Weight (kg) 13 14 14 20 25
Dimensions (hwd) (mm) 231x158x400 340x158x485
Operating temperature O °C - 40 °C
Relative humidity < 95% non condensing
Protection Overload - short-circuit - overvoltage - undervoltage - temperature - low battery
Communication USB / RS232
Safety compliance EN 62040-1-1 and Directive 73/23 EEC, EN 62040-3
EMC conformance EN 62040-2 and Directive 89/336
Surge capability IEC 801-5 6 KV 1.2 / 50 µs; 3KA 8/20 µs differential
Colour Light grey RAL 7035
Noise <40 dBA at 1 m
Extended runtime solutions – yes
DETAILS
Output sockets
PC/telephone
line/modem
protection
USB connector
Selector switch (RS232/USB)
Mains input
Serial
interface port
Slot for network
card
Selector switch (RS232/USB)
USB connector
PC/telephone
line/modem
protection
Serial
interface port
Output sockets
Mains input
IT Range