15
DIALOG PLUS
DLP 70 DLP 100
DLP 100 ER
DLP 150
DLP 200
DLP 200 ER
DLP 300
DLP 300 ER
MODELS DLP 70 DLP 100
DLP100ER
DLP 150 DLP 200
DLP200ER
DLP 300
DLP300ER
POWER 700VA/490W 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W
INPUT
Rated voltage 220 - 230 - 240 Vac
Minimum voltage range
110V up to 60% of load / 120V from 60% to 70% of load
140V from 70 to 80% of load / 160V from 80% to 100% of load
Maximum voltage 300 Vac
Rated frequency 50/60 Hz ± 5Hz
Power factor > 0.97
Input current Sinewave
BY PASS
Voltage range 180 - 264 Vac
Frequency range Selected frequency ±5Hz
BATTERIES
Recharge time 2-4 h - 2-4 h 4 h - 4 h -
Type VRLA AGM Maintenance-free lead-acid
OUTPUT
Rated voltage selectable 220, 230 or 240 Vac ±1.5%
Waveform Sinewave
Voltage distortion < 2%
Frequency 50 or 60 Hz auto sensing
Crest factor 3 : 1
Overloads 110% 30’; 130% 30”; 150% 10”
ENVIRONMENTAL
Weight (kg) 12 14 8 19 34 14 35 15
Dimensions (hwd) (mm) 231x158x400 231x158x500 340x192x460
Operating temperature O °C - 40 °C
Relative humidity < 95% non condensing
Protection Overload - short-circuit - overvoltage - undervoltage - temperature - low battery
Communication RS232 + communication interface slot
Compliance EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
Surge capability 3KA 8/20 µs
Colour metallic grey (silver)
Noise <40 dBA
OPTIONS
Extended runtime solutions – yes
Isolation transformer box (hwd) (mm)
231x158x434 340x158x460
Output sockets
Input socket
Telephone/IT
network protection
Serial interface
External battery
pack socket
Slot for SNMP
network adapter card
Serial interface
External battery pack socket
Slot for SNMP network adapter card
Output sockets
Input socket
Telephone/IT network protection
Thermal fuses
DETAILS
IT Range