29
DIALOG ACTIVE RACK
MODELS DAR 50 DAR 75 DAR 100 DAR 150 DAR 200
POWER 500VA / 335W 750VA / 500W 1000VA / 670W 1500VA / 1000W 2000VA / 1340W
INPUT
Rated voltage 220 ÷ 240 Vac
Voltage range 220 ÷ 240 Vac (-25%, +21%)
Frequency 50/60 Hz auto sensing ± 5Hz
OUTPUT
Rated voltage 230 Vac ± 2%
Voltage on mains operation automatically corrects output voltage from -15% to +15% with input fluctuation within ±25%
Frequency 50 - 60 Hz auto sensing
Voltage on battery operation 230 Vac (± 5%)
Waveform Sinewave with distortion <2%
Output sockets 4 IEC 320 10A
BATTERIES
Type VRLA AGM Maintenance-free lead-acid
Recharge time 6-8 h
ENVIRONMENTAL
Weight (kg) 19 20 21 26 34
Dimensions (hwd) (mm) 2Ux19”x450
3Ux19”x450
Operating temperature O °C - 40 °C, ideal for battery 15 °C - 25 °C
Relative humidity < 95% non condensing
Protection Overload - short-circuit - overvoltage - undervoltage - temperature - low battery
Safety compliance EN 62040-1-1 and Directive EEC 73/23, Directive EEC 93/68; EN 62040-3
EMC Conformance EN 62040-2 and Directive EEC 89/336
Communication USB / RS232 + communication interface slot
Surge capability IEC 801-5 6 KV 1.2 / 50 µs; 3KA 8/20 µs differential
AC/AC Efficiency 98 %
PC NET/Tel protection surge protection Net/Tel type RJ45/RJ11
Colour Dark grey RAL 5004
Noise <40 dBA aT 1 m
OPTIONS
Extended runtime solutions – yes
External manual bypass
(hwd) mm/kg
2Ux438x360 - rack version weighs 6,8 (see Multipass)
180x300x115 - box version weighs 3,3 (see Multipass)
Product characteristics can be customised to meet client specifications.
DETAILS
Battery
expansion socket
Battery pack
Telephone/IT power
protection
USB port
Selector switch
RS232/USB
RS232
Serial port
Input
socket
Output
plugs
Interface
card slot
NET-TEL Range
FRONT
BACK
Comentarios a estos manuales