40
MASTER PLUS
MODELS MP 100 MP 120 MP 160 MP 200
POWER (kVA) 100 120 160 200
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phasee
Voltage tolerance 400 V ± 20%
Frequency 45 ÷ 65 Hz
Power factor >0.95 in the 12MP HC version
Current distortion <3% in the 12MP HC version
Soft start 0 ÷ 100% in 120’’ configurable
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from the front panel)
Standard features Back Feed protection; separable bypass line
BATTERY
Type Lead, flooded and VRLA AGM / GEL; NiCd
AC ripple <1%
Temperature compensation -0,5 Vx °C
OUTPUT
Rated power (kVA) 100 120 160 200
Active power (kW) 80 96 128 160
Number of phases 3 + N
Nominal voltage 380 - 400 - 415Vac three-phase + N
Static stability ± 1%
Dynamic stability ± 5% in 10 msec.
Voltage distortion with linear load <1%
Voltage distortion with distorting load <3%
Frequency 50 or 60 Hz configurable
Waveform Sinusoidal
Peak factor 3:1
Overload 110% for 60’; 125% for 10’; 150% for 1’
SYSTEM
Remote signalling Voltage-free contacts
Remote commands EPO and bypass
Communication double RS232 + remote contacts + 2 communication interface slots
Performance Up to 94%
Dimensions (HxLxD) (mm) 1900x800x800
Weight (kg) 600 650 750 800
Noise level 63 ÷ 68 dBA a 1 m
Operating temperature 0 °C / +40 °C
Relative humidity <95% non condensing
Protection rating IP20
Colour RAL 7035
Standards
Directives EEC 73/23 - 93/68 - 89/336
Safety IEC EN 62040-1; EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification as per IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111
INDUSTRY Range